Measurement-computing CB-COM-7012 Manual do Utilizador Página 60

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 72
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 59
60
CB-7012, CB-7014, CB-7017 Users Manual
2.37 ~AA0
Description: Read Module Status
Syntax: ~AA0[CHK](cr)
~ Delimiter character
AA Address of module to read (00 to FF)
0 Command for module status
Response: Valid Command: !AASS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
SS module status, 00=host watchdog status is clear, 04=host
watchdog status is set. The status is stored in EEPROM
and can only be reset by the ~AA1 command.
Example:
Command: ~010 Receive: !0100
Read Address 01 module status, return 00.
Command: ~020 Receive: !0204
Read Address 02 module status. A return of 04 means the
host watchdog timeout status is set.
Related Command:
Sec.2.38, ~AA1; Sec.2.40, ~AA3EVV
Related Topic:
Set.3.2, Module Status; Sec.3.3, Dual Watchdog Operation