CB-7012, CB-7014, CB-7017 Users Manual
2.24 @AADA
Description: Disable Alarm
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AADA[CHK](cr)
@ Delimiter character
AA Address of module to set (00 to FF)
DA Command for disable alarm
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: @01DA Receive: !01
Disable Address 01 alarm; return successful.
Related Command:
Sec. 2.21, @AAEAT
Related Topic:
Sec. 3.6, High/Low Alarm