
49
CB-7012, CB-7014, CB-7017 User’s Manual
2.26 @AARH
Description: Read High Alarm
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AARH[CHK](cr)
@ Delimiter character
AA Address of module (00 to FF)
RH Command for reading high alarm
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command.
? Delimiter for invalid command.
AA Address of responding module (00 to FF)
(Data) high alarm value is in engineering units format.
Example:
Command: @01RH Receive: !01+10.000
Read Address 01 high alarm; return +10.000.
Related Command:
Sec. 2.22, @AAHI
Related Topic:
Sec. 3.6, High/Low Alarm
Comentários a estes Manuais