CB-7012, CB-7014, CB-7017 Users Manual
2.29 @AACE
Description: Clear Event Counter
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AACE[CHK](cr)
@ Delimiter character
AA Address of module (00 to FF)
CE Command to clear event counter
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: @01RE Receive: !0101234
Read Address 01 event counter; returns 1234.
Command: @01CE Receive: !01
Clear Address 01 event counter, return successful.
Command: @01RE Receive: !0100000
Read Address 01 event counter, return 0.
Related Command:
Sec. 2.28 @AARE
Related Topic:
Sec. 3.4 Digital Input and Event Counter