Measurement-computing CB-7011 Manual do Utilizador Página 56

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 68
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 55
56
CB-7011/CB-7011D, CD-7018 Users Manual
2.34 ~AA1
Description: Reset Module Status
Syntax: ~AA1[CHK](cr)
~ delimiter character
AA address of setting module (00 to FF)
1 command for reset module status
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: ~010 Receive: !0104
Read address 01 module status, return 04, host watchdog
timeout flag is set.
Command: ~011 Receive: !01
Reset address 01 module status, return success.
Command: ~010 Receive: !0100
Read address 01 module status, return 00, Module Status is
clear.
Related Command:
Sec. 2.32 ~**, Sec. 2.33 ~AA0
Related Topic:
Sec. 3.2 Module Status, Sec. 3.3 Dual Watchdog Operation
Vista de página 55