CB-7011/CB-7011D, CD-7018 Users Manual
2.26 @AADA
Description: Disable Alarm
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AADA[CHK](cr)
@ delimiter character
AA address of setting module (00 to FF)
DA command for disable alarm
Response Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: @01DA Receive: !01
Disable address 01 alarm, return success.
Related Command:
Sec. 2.23 @AAEAT
Related Topic:
Sec. 3.6 High/Low Alarm