CB-7011/CB-7011D, CD-7018 Users Manual
2.30 @AARE
Description: Read Event Counter
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AARE[CHK](cr)
@ delimiter character
AA address of reading module (00 to FF)
RE command for reading event counter
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
(Data) event counter value, from 00000 to 65535.
Example:
Command: @01RE Receive: !0101234
Read address 01 event counter, return 1234.
Related Command:
Sec. 2.31 @AACE
Related Topic:
Sec. 3.4 Digital Input and Event Counter