47
CB-7011/CB-7011D, CB-7018 User’s Manual
2.25 @AALO(Data)
Description: Set Low Alarm
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AADI[CHK](cr)
@ delimiter character
AA address of setting module (00 to FF)
LO command for setting high alarm value
(Data) high alarm values, data format is in engineer unit format.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: @01LO-2.5000 Receive: !01
Set address 01 low alarm -2.5000, return success.
Related Command:
@AAEAT (Sec. 2.23), @AARL (Sec. 2.29)
Related Topic:
High/Low Alarm (Sec. 3.6)