Measurement-computing PCM-DAS16x/16 Manual do Utilizador Página 26

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 40
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 25
6.2 WIRING CONFIGURATIONS
Combining all the grounding and input type possibilities provides us with the follow-
ing potential connection configurations. The combinations along with our recommen-
dations on usage are shown in the chart below.
RecommendedDifferential Inputs
Already Isolated
Grounds
AcceptableSingle-ended Inputs
Already Isolated
Grounds
Unacceptable without
adding Isolation
Differential Inputs
Common Mode
Voltage > +/-10V
Unacceptable without
adding Isolation
Single-Ended Inputs
Common Mode
Voltage > +/- 10V
RecommendedDifferential Inputs
Common Mode
Voltage < +/-10V
Not RecommendedSingle-Ended Inputs
Common Mode
Voltage < +/-10V
AcceptableDifferential InputsCommon Ground
RecommendedSingle-Ended InputsCommon Ground
OUR VIEW
INPUT
CONFIGURATION
GROUND
CATEGORY
22
Vista de página 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 39 40

Comentários a estes Manuais

Sem comentários