2.3 $AA5
Description: Read Reset Status
Command: $AA5[CHK](cr)
$ Delimiter character
AA Address of reading module (00 to FF)
5 Command for reading reset status
Response: Valid Command: !AAS[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no
response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
S Reset status, 1 = the module is been reset; 0 = the
module is not been reset.
Example:
Command: $015 Receive: !011
Read address 01 reset status, returns first read.
Command: $015 Receive: !010
Read address 01 reset status, returns no reset occurred.