Measurement-computing CB-COM-7021 Manual do Utilizador Página 45

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 76
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 44
45
CB-7021, CB-7022, CB-7024 Users Manual
2.15 #AAN(Data)
Description: Output Analog Value for Channel N
Note: The command is for CB-7022 and CB-7024 only.
Syntax: #AAN(Data)[CHK](cr)
# Delimiter character
AA Address of output module (00 to FF)
N Output channel (0 to 1 for CB-7022, 0 to 3 for CB-
7024)
(Data) Analog output value, reference Sec. 1.10 for its format.
Response: Valid Command: >[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Ignore Command: ![CHK](cr)
Syntax error or communication error may get no
response.
> Delimiter for valid command
? Delimiter for invalid command. When the (Data) is out
of range, and the output will go to the closest value in the
module’s range.
! Delimiter for the module’s host watchdog status is set,
and the output command will be ignored.
AA Address of response module (00 to FF)
Example for CB-7022:
Command: $012 Receive: !013F0600
Read address 01 configuration, returns multichannel output,
9600 bps and engineering unit format.
Command: $0190 Receive: !0110